出口數目同闊度點計?(NSW)
exit-count-and-width · 州別版02數字表
| 要求 | 數值 | 條文 | 適用情況 |
|---|---|---|---|
| 每層最少出口數 | 1 count | D2D3 Number of exits required + D2D5 Exit travel distance… | every building, every storey — D2D3(1) |
| Class 2–8 指定情況最少出口數 | 2 count | —(未引條文) | storeys meeting D2D3(2) triggers (e.g. effective height >25 m, >50 persons per D2D18) |
| 單向走火最大距離 | 20 m | —(未引條文) | Class 5-9 any point on floor to exit or split point — D2D5(3)(a) |
| 雙向分岔後最大距離 | 40 m | —(未引條文) | travel in different directions to 2 exits — D2D5(3)(a) |
| Class 5/6 單出口最大距離 | 30 m | —(未引條文) | single exit serving storey at level of access to road/open space — D2D5(3)(b) |
| 出口/走火通道最小淨闊 | 1 m | —(未引條文) | each required exit or path of travel (except doorways) — D2D8(1)(a) |
| 闊度加碼起點(容納人數) | 100 persons | —(未引條文) | aggregate width scaling begins — D2D8(2) |
| 每人加闊幅度(100–200 人段) | 250 mm | —(未引條文) | per 25 persons (or part) in excess of 100 — D2D8(2)(a) |
| >200 人總闊起點 | 2 m | —(未引條文) | more than 200 persons — D2D8(3) |
| >50 人樓層加出口觸發 | 50 persons | —(未引條文) | storey/mezzanine accommodating more than 50 persons per D2D18 — D2D3(2)(a)(vi) |
03Inspector 實睇乜
- 每層出口數目夠唔夠(人數 >50/>100 都係觸發線)
- 最遠一點行到出口係咪 ≤20m(單向)/40m(雙向)
- 出口淨闊有冇 1m(計門後掃手位同貨物)
- 走火通道一路到街有冇收窄/擺貨
- 出口門開向同 push bar 係咪按人數要求
04做錯幾多錢 + 幾時要決定
做錯成本:開新出口門/改門斗:A$3,000–12,000;fire engineer 重做 egress 報告:A$2,000–6,000;驗收唔過延遲開業以星期計。
幾時要決定:平面圖階段 fire engineer 就要核算人數同出口;final inspection 實尺量闊度。
最常撞板:
- 改間隔後最遠座位行到 25m 冇人發現
- 出口通道俾 storage 收窄過 1m
- 人數加咗但出口冇加/冇加闊
- 唯一出口樓層加建 mezzanine 後變兩層唔夠出口
05州別差異
| 州 | 數值 | 備註 |
|---|---|---|
| NSW | — | state_delta: none — NSW 直接適用全國條文(無州級差異;registry 快照為證) |
| VIC | — | state_delta: none — base 快照為證;未發現 VIC 專屬差異 |
| QLD | — | state_delta: none — 已對 QLD 16 份快照(Brisbane/Bundaberg/CHRC DCG、SafeFood 3.2.3、OLGR liquor、noise limits、disability access、CCTV)逐條比對,未發現 QLD 專屬差異 |
| WA | — | state_delta: none — 已對 WA 快照集(WA Health design hub、Vincent/South Perth/Fremantle/Cockburn/Northam council guides、Cockburn exhaust hood、DLGSC plans-specs、Water Corp PUB6B、SWA COPs)逐條比對,未發現「exit-count-and-width」有 WA 專屬數值差異 |
| SA | — | state_delta: none — 已對 SA 快照集(EHA Welcome Pack 2022、SA Health food business hub、SA Health hairdressing standards、NCC 2022 Vol1 SA variations 節、NCC 2022 SA Part H10、EPA SA 279/21 music noise guideline)逐條比對,未發現「exit-count-and-width」有 SA 專屬數值差異 |
| TAS | — | state_delta: none — 已對 TAS 快照集(NCC 2022 TAS Part H102 food premises、NCC 2022 TAS Part D4 variation、Clarence CC Food Business Construction Guide 2025、Southern Midlands Food Business Information Guide 2025、TasWater Pre-Treatment Guideline 2022、EPA Tas Noise Regulations)逐條比對,未發現「exit-count-and-width」有 TAS 專屬數值差異 |
| ACT | — | state_delta: none — 已對 ACT 快照集(ACT Food Business Fit-out Guide Aug 2025、ACT Food Business Inspection Manual、NCC 2022 全國條文)逐條比對,未發現 ACT 專屬數值差異 |
| NT | — | NT 無已核實州級差異;全國基準適用。 |
06常見問題
NCC 2022 D2D3:每層每個 building 至少要有 1 個 exit;Class 2–8 樓層喺多種情況(例如 effective height >25m、每層容納人數過 50 等)要加至唔少過 2 個 exit。D2D5(3):Class 5–9 建築樓面任何一點去出口(或去雙向分岔點)唔超過 20m,行雙向時其中一個出口最遠 40m;Class 5/6 單出口可放寬到 30m。D2D8:每個 required exit/走火通道淨闊最少 1m;樓層容納 >100 人開始要加闊——100 人以上每 25 人(不足當 25)加 250mm,>200 人改為 2m 起再加每 75 人 500mm(斜道級係每 60 人)。人數按 D2D18 計。出口闊度一路去到街口唔可以收窄(D2D10)。設計由 fire engineer/building surveyor 按人數核算。
出口數目同闊度點計?
每層最少 1 個出口;多數商業樓層要 2 個;走火距離上限 20m(雙向 40m);出口淨闊最少 1m。
呢條係法定要求定係行業做法?
有官方文件、條款號、快照同 sha256,數值喺原文 grep 得到。
做錯會點?要幾時決定?
開新出口門/改門斗:A$3,000–12,000;fire engineer 重做 egress 報告:A$2,000–6,000;驗收唔過延遲開業以星期計。 時間點:平面圖階段 fire engineer 就要核算人數同出口;final inspection 實尺量闊度。